> เทคนิคการเลือกขนาดของสายไฟ > การเลือกใช้ FUSE กับขนาดและความยาวของสายไฟ

การเลือกใช้ FUSE กับขนาดและความยาวของสายไฟ

Electrical Cable Sizing Chart

 

  • Step 1. DC Amps: Locate the flow of current in amps of your circuit along the top of the chart below.

     
  • Step 2. Circuit Type: Select the correct type of circuit. Examples of Non Critical circuit are bait pumps,
    windlasses, general lighting, general appliances. Examples of Critical circuits are bilge blowers, panel main feeders, navigation lights, electronics.


     
  • Step 3. Cable Length: Find the correct length range of cables. Please note that the length is the total length of the positive and negative wires. I.E. Distance from battery to appliance multiplied by 2.

     
  • Step 4. Correct Cable Size: Intersect the DC Ampere with the cables length range to identity the correct coloured symbol.


     

Electrical Cable Size

 

Electrical Cable Size

 

 

Cables impedance calculation

 

Impedance is calculated by below formula:

This method calculates the impedance when the cable and load power factor is the same, this scenario is worse case power factor.

cable sizing calculator uses the resistance Rc from Table 35 in AS/NZS 3008-2017. The reactance for single core cables is selected from the flat

 


 

Loop impedance calculation

The maximum loop distance is calculated by below formula:

 

Where:

  • V is the single phase voltage.
  • Imin is the minimum alowable tripping current of the MCB or other protection device.
  • Zc is the cable impedance in Ohm/km.

 

 

Voltage drop calculation

The three phase AC voltage drop is calculated as below

The single phase AC voltage drop is calculateda as below

Where I is the load current, L is the distance, and Zc is the cable impedance in Ohm/km.

 

Short circuit calculation

The short circuit capacity of the cables is calculated according to AS/NZS 3008-2017

Where:

  • I is the short circuit current capacity in amperes,
  • K is a constant that is selected from Table 52 in AS/NZS 3008-2017.
  • S is the cross sectional area of the conductor.
  • t is the short circuit duration in seconds.

 

Electrical Cables Size & Current Rating Chart

Cross Section (mm2) Approximate Overall Diameter (mm) Current Rating
Single Phase (Amps) Three Phase (Amps)
1.5 2.9 17.5 15.5
2.5 3.53 24 21
4 4.4 32 28
6 4.68 41 36
10 5.98 57 50
16 6.95 76 68
25 8.7 101 89
35 10.08 125 110
50 11.8 151 134
70 13.5 192 171
95 15.7 232 207
120 17.4 296 239
150 19.3 300 262
185 21.5 341 296
240 24.6 400 346
300 27.9 458 394
400 30.8 546 467
500 33.8 626 533
630 37.6 720 611
International standard wire size Chart (IEC 60228)
0.75 mm² 4 mm² 0.5 mm² 1 mm² 2.5 mm² 1.5 mm²
70 mm² 6 mm² 25 mm² 185 mm² 35 mm² 400 mm²
95 mm² 1000 mm² 10 mm² 800 mm² 150 mm² 50 mm²
300 mm² 120 mm² 500 mm² 16 mm² 630 mm² 240 mm²